A water meter records the volume of cold or hot water in a closed pipe. Choose and install it correctly so the utility accepts it for billing and the assembly passes verification.

What a water meter is and which metering assemblies exist

A water meter is a measuring instrument. For billing in Ukraine it is legally regulated: the type must comply with the technical regulation, and a meter in service must be verified periodically.

The Law of Ukraine “On commercial metering of heat and water supply” distinguishes two levels. A commercial metering assembly sits at the service entrance to a building or a detached house: the operator bills the building as a whole from that meter. A distribution meter in an apartment or office allocates that building volume among consumers. In an apartment building connected to external networks or with autonomous water supply, premises are fitted with distribution meters for drinking water and, where provided, hot water — except in the cases set out in the law.

The water meters catalogue covers apartments, houses and building inlets. An engineer matches diameter, temperature, flow range and connection to the project or the utility’s conditions.

Meter types: impeller, turbine and non-mechanical

The most common meters in apartments and on small inlets are impeller meters. Flow turns an impeller, and the rotation is transmitted to the register. Single-jet models suit moderate flow: typical DN 15 examples are the BAYLAN KK-12 cold-water meter and the BAYLAN KK-12S hot-water meter. Multi-jet meters split the flow before the impeller and often tolerate an uneven profile better; they are more common on larger sizes.

Registers are dry-dial or wet-dial. In a dry-dial meter the register is separated from the water, usually by a magnetic coupling, so it is easier to read. A wet-dial mechanism is flooded. The permitted design follows the datasheet and the utility.

On building inlets and larger process lines, Woltman turbine meters are used, usually flanged. Ultrasonic or electromagnetic meters are chosen for a wider range, no moving parts in the flow, or remote reading. Straight-run, power and interface limits come only from the manufacturer’s documents.

How to choose a meter: diameter, flow, temperature and orientation

Selection starts from the duty of the metering point, not from the shelf.

  • Nominal diameter DN and connection type. Apartments most often take threaded DN 15 or DN 20; building inlets take a larger threaded or flanged size. Nominal bore does not always match the body thread: many DN 15 impeller meters use G 3/4. Check the datasheet before ordering unions.
  • Flow rate. Harmonized standards (ISO 4064 / OIML R49) define Q1 as minimum flow, Q2 transitional, Q3 permanent and Q4 overload. The range R = Q3/Q1: a higher R means the meter records low flows better. Older class letters A, B and C still appear; use the actual R, not the letter alone. A Qn rating must not be treated as Q3 automatically.
  • Temperature class. A cold-water meter must not be fitted on a hot-water pipe. The BAYLAN KK-12 product page states a medium temperature up to 50 °C; the KK-12S hot-water version is listed up to 90 °C. Any short-term overshoot, if allowed, is only in that model’s datasheet. Whether a hot-water meter may be used on cold water must be confirmed by the manufacturer and the utility.
  • Mounting orientation. Horizontal (H) and vertical (V) positions often have different R values; vertical mounting may be narrower. Do not install the meter at an angle unless the datasheet allows it. Flow must follow the arrow on the body.
  • Face-to-face length L and union set. Apartment DN 15 meters commonly have L = 110 mm, DN 20 meters 130 mm, and larger impeller meters 260 or 300 mm. Many models ship without connectors: a DN 15 meter needs a separate brass union set with nuts of the same diameter, with gaskets. The set must match the meter and the pipe.
  • Remote reading. If readings go to a control room or a customer portal, specify a pulse output or a module that matches the utility’s system — not the other way around.

Working pressure, pressure loss and other limits come from the datasheet, not from a neighbour’s meter. Billing use requires conformity documents and initial verification for that instrument.

Comparison table of water-meter types

Type Typical use Connection What to check
Single-jet impeller Apartments and low-flow points, usually DN 15–20 Threaded H/V orientation and R only from the datasheet; unions often come separately
Multi-jet impeller Apartments, risers, medium-size inlets Thread, sometimes flange More tolerant of uneven flow; check face-to-face length against the gap
Woltman turbine Building inlets, process lines, large DN Usually flanged Straight runs, water quality and orientation — from the datasheet and the network specification
Ultrasonic or electromagnetic Wider range, no moving parts in the flow, or remote reading Thread or flange Power, interface and straight-run limits — only from the model documentation

Common apartment sizes for threaded impeller meters in the catalogue are DN 15 with permanent flow Q3 2.5 m³/h and length 110 mm, and DN 20 with Q3 4.0 m³/h and length 130 mm. Larger impeller models often appear as DN 25 / Q3 6.3 m³/h / 260 mm, DN 32 / Q3 10.0 m³/h / 260 mm, DN 40 / Q3 16.0 m³/h / 300 mm and DN 50 / Q3 25.0 m³/h / 300 mm. These are guides, not a rule for every brand: some ranges are still marked Qn, and flanged turbine meters have a different length. Confirm the size from the datasheet and project.

How to assemble and install a metering station

DBN V.2.5-64:2012 with Amendment No. 1, section 13, sets the location at a building entrance. Install the meter after the pipe enters the building, behind the first wall or after crossing no more than one internal wall, in a room with lighting and an air temperature of at least 5 °C. The position must allow reading, verification, removal and sealing. An apartment assembly is fitted on the branch into the premises, usually just after the inlet.

A typical apartment assembly includes:

  • isolating valves upstream and downstream — usually brass ball valves of the matching size;
  • a mesh or Y-pattern strainer upstream, so particles do not damage the impeller;
  • the meter with its union set and gaskets, aligned with the flow arrow;
  • between the meter and the next downstream valve — a drain (test) cock with a permanently fitted cap; on building inlets the DBN also recommends a pressure gauge;
  • a threaded check valve — mandatory where a building has several looped inlets with meters; on an apartment inlet it often prevents cross-flow between the cold and hot networks.

If a pressure-reducing valve is required, place it relative to the valves and the meter as the DBN requires. See also “Water pressure reducer: why you need one, how to install and adjust”, “Filters and strainers: why they are needed and how to install them” and “Check valve types: how they work and how to choose”.

Straight lengths upstream and downstream are defined by the datasheet (for example U0/D0 or U5/D3). The BAYLAN KK single-jet datasheet states U0, D0 — the manufacturer does not require straight runs. Many utilities still ask for at least 5 nominal diameters of straight pipe upstream, with no valves, bends, tees or check valves on that length. Apply the stricter of the datasheet and the operator’s rules. If the meter is smaller than the pipe, the reducer should be conical and, under typical rules, outside the assembly itself. Fix the pipework so that shift, bending and vibration are not transferred to the body, and fill the line gradually.

After installation the service provider accepts the billing assembly: it checks the layout and documents, seals the connections, and records the initial reading and the next verification date. Do not break seals yourself; apply first so removal and resealing are logged. Have commercial and distribution assemblies installed by organizations the service provider recognizes.

Water-meter verification in Ukraine

Water meters are legally regulated instruments subject to periodic verification. Ministry of Economic Development and Trade of Ukraine Order No. 1747 of 13 October 2016 sets a four-year interval for both cold- and hot-water meters. Count the interval from the verification date (initial or previous periodic) in the passport, certificate or customer portal — not from the shop purchase date if the two dates differ.

Only authorized metrology centres and laboratories may carry out verification. After a pass result, a certificate is issued or a mark is applied as prescribed. If the meter fails, it is repaired or replaced, verified after repair, and only then reinstalled and sealed.

Periodic verification, servicing and repair of apartment heat- and water-metering assemblies, including removal, transport and reinstallation, are paid for by the owners unless a contract provides otherwise — as set out in the Law of Ukraine “On metrology and metrological activity”. For building-level commercial metering, procedure and funding follow the commercial metering law and contracts with the network operator.

During martial law the Cabinet of Ministers has changed the deadlines for submitting instruments for verification. Confirm the current procedure with the service provider and the resolution in force, not only the passport date.

Common mistakes in selection and installation

  • Fitting a cold-water-only meter on a hot-water pipe.
  • Sizing from the pipe diameter without checking Q3 against actual flow: an undersized meter runs overloaded, an oversized one is poorer at low flows.
  • Vertical mounting of a model that has a different R in that position, or installing the meter at an angle.
  • No strainer upstream of the meter, or placing it downstream.
  • Forgetting the union set, or using unions of a different size or thread from the body.
  • Omitting the straight lengths required by the datasheet or the utility.
  • No isolating valves on both sides — verification or replacement then means shutting a riser or the inlet.
  • Assembling the station but not calling the service provider to accept and seal it, so the readings are not used for billing.

Frequently asked questions

Which water meter should be installed in an apartment — DN 15 or DN 20?

Most apartments take a threaded impeller meter DN 15 with Q3 2.5 m³/h and length 110 mm, if the supply pipe and the flow allow it. Choose DN 20 with Q3 4.0 m³/h and length 130 mm when the pipe or the flow is larger. Confirm the size from the actual pipe, the datasheet and the utility’s requirements, not by eye.

Can a cold-water meter be installed on a hot-water pipe?

No. The temperature class must match the medium. A cold-water meter rated, for example, to 50 °C must not be used outside its datasheet on a hot-water system. Hot water needs a matching model; take temperature limits only from that product’s datasheet.

What is the verification interval for water meters in Ukraine?

Four years for both cold- and hot-water meters, according to Ministry of Economic Development Order No. 1747. The period runs from the verification date in the instrument documents. During martial law, confirm the current procedure with the service provider.

Are a strainer and a straight pipe run required upstream of the meter?

A coarse strainer upstream of the instrument is required by the building code and by network operators, and is recommended by manufacturers. Straight lengths are defined by the datasheet; many utilities also ask for at least 5 diameters of straight pipe upstream. Follow the stricter requirement.

Who pays for apartment-meter verification, and what should be done when the interval expires?

Unless a contract provides otherwise, the owner pays for periodic verification, removal, transport, repair and reinstallation of apartment water-metering assemblies. Only authorized laboratories may perform the verification. When the interval expires, apply to the service provider to have the seals removed; the meter is verified or replaced, then refitted and resealed. Without this, readings may not be accepted for billing.